M.b Miranzadeh, M Sabahi Bidgoli, A.r Zarfeshani, M Heidari,
Volume 4, Issue 4 (3-2012)
Abstract

Background and Objectives Autoclaving is one of  the methods which sterilizes infectious solid wastes. Since variety of parameters such as temperature, time, and pressure influence autoclave performance, this study was carried out to evaluate the parameters and set optimum condition for the autoclave apparatus  applied in Shahid Beheshti Hospital in Kashan.
Materials and Methods: In this descriptive-analytical study, the performance of subjected autoclave was surveyed based on biological index and through setting 144 tests. Variables were packaging type in two groups (open and wrapped), loading type in three groups (light, medium and heavy), and four temperature-time features in fixed pressure equal to 101 kpa. Biological index was ATCC 7953 which contained Stearotermophilus Geobacillus spores. Finally obtained results were analyzed by Chi-Square test.
Results: The results of statistical test showed that there isn't any meaningful relation between packaging type of waste, system loading, and efficiency of sterilization(P>0.05),while meaningful relation was found between system performance and variety states of temperature-time feature(P<0.05), illustrating temperature and time effects in fixed pressure on sterilization of solid waste.
Conclusion: Based on the results, the best autoclave operational condition for sterilizing infectious solid wastes are: temperature-time equal to 10 min-140°C and 15 min-134°C in fixed pressure of 101 kpa, respectively. It was also revealed that temperature-time condition suggested by manufactory, i.e. 20min-121°C, is not sufficient for complete sterilization of solid waste.


Abdolrahman Gharanjic, Ramazan Ali Dianati Tilaki, Samaneh Dehghan, Abutaleb Bay, Fathollah Gholami-Borujeni,
Volume 18, Issue 2 (9-2025)
Abstract

Background and Objective: Proper operation and maintenance of hospital waste sterilization devices are crucial for preventing the spread of infections and hazardous diseases, as well as for safeguarding public health and the environment. This study aims to assess the operational and maintenance status of medical waste sterilization devices in public and private hospitals in Golestan Province.
Materials and Methods: This descriptive-analytical study was conducted in 17 public and 6 private hospitals in Golestan Province, all of which were equipped with vacuum steam autoclaves (without shredders) for medical waste sterilization. Monthly microbiological sampling was performed by an accredited environmental laboratory. Data were collected using standardized questionnaires and personal interviews, with results analyzed using frequency distributions, percentages, and central tendency measures.
Results: The overall microbial sterilization performance of the devices was 97.07%, indicating high efficacy in waste treatment. When comparing hospital types, public hospitals demonstrated a 96.93% satisfactory sterilization rate, while private hospitals performed slightly better at 97.22%. Regarding preventive maintenance, compliance was suboptimal, with public hospitals adhering to maintenance protocols 68.62% of the time, compared to 77.77% in private hospitals. Additionally, the sanitary conditions of sterilization device locations met required standards in 94.11% of public hospitals but only 69.05% of private hospitals, suggesting variability in facility upkeep.
Conclusion: To ensure device effectiveness and minimize risks in hospital waste management, implementing preventive maintenance programs and providing continuous staff training on proper device use are essential.
 