Mahdi Jamshidi Rastani, Farshid Ghorbani Shahna, Abdolrahman Bahrami, Somayeh Hosseini,
Volume 6, Issue 2 (6-2016)
Abstract

Introduction: Adherence to the design values and ventilation standards (VS) after installing and also maintaining continuous work of ventilation system with maximum performance throughout its life are amongst the reasons of ventilation systems monitoring. Therefore, the aim of this study was to evaluate performance of local exhaust ventilation system for control of dust by measuring the operating parameters and also to compare it with ventilation standards (VS) and design values.

Material and Method: The present research is a descriptive and cross-sectional study, conducted in three sections of measuring, monitoring and evaluating the operating parameters on hoods, channels and fan of ventilation system based on the current status of the system, documentation (design), and recommended standards (VS). Static pressure, velocity pressure, surface area, and flow rate were measured based on the recommendations of various sources and ACGIH industrial ventilation manual, and the data were compared with the design and recommended values, using the SPSS software version 16.  

Result: The results of paired sample t-test between flow rate and velocities of design and current status, showed significant differences in various parts. Accordingly, the results revealed a reduction of more than 50% in the design duct velocity compared to the current duct velocity, while design duct velocity is 1.3 more than the standard duct velocity of current status, and current duct velocity is about 65% of standard duct velocity.

Conclusion: The reduction and nonconformity of the results of measurements of operating parameters (after a minimum of two decades) with design and standard values are corroborant and sufficient reason for obstructions, abrasions, leaks, imbalance of system ducts and their inefficiency in some branches. Since there is no base line measurements for system (supposing that the system worked with maximum amounts of setup time), one of the reasons for these changes can be attributed to lack of schedule for regular and appropriate maintenance.


Mehrdad Helmi Kohnehshahri, Farideh Golbabaei, Somayeh Farhang Dehghan, Rezvan Zendehdel, Alireza Abbasi, Zahra Yadegar,
Volume 15, Issue 2 (7-2025)
Abstract

Introduction: With the advancement of industries and increased use of metalworking fluids, controlling pollutants generated by machining operations has become increasingly challenging. This study aimed to address these challenges by designing an air filtration system designed specifically for this purpose.
Material and Methods: A local exhaust ventilation system was developed based on the VS-80-12 ACGIH standard, tailored to the working conditions and air sampling of the environment. The filtration system includes an aluminum pre-filter, an E11 class filter, and a nanofiber filter incorporating a metal-organic framework. The performance of the system was evaluated by measuring the numerical concentration of particles and the mass concentration of oil mist at both the inlet and outlet. The results were then compared to those obtained from an E1 class filter.
Results: The results obtained from XRD and FTIR analyses showed that ZIF-8 had high crystallinity and was successfully incorporated into the structure of the fibrous media filter containing metal-organic framework. The evaluation revealed that the filtration system effectively removed pollutant particles at their source. Notably, the initial efficiency for larger particles reached 100%, while the average removal efficiency for particles smaller than 2.5 microns was 99%.  
Conclusion: In conclusion, the combination of nanofiber filters with a metal-organic framework and aluminum pre-filters presents an effective solution for controlling particulate pollutants from machining operations. However, further research is necessary to comprehensively assess the system’s performance, particularly regarding dust loading capacity. Future studies should also explore the effects of various factors, such as airflow rate and the type of metalworking fluid, on the system’s efficacy.